Studi Pengaman Busbar Pada Gardu Induk Amlapura I Made Dian Purnawan; I G Dyana Arjana; I W Rinas
Jurnal Teknologi Elektro Vol 15 No 1 (2016): (January - June) Majalah Ilmiah Teknologi Elektro
Publisher : Universitas Udayana

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (200.975 KB) | DOI: 10.24843/MITE.2016.v15i01p07

Abstract

Busbar safety is a protection system that plays an important role in securing the disruption of the busbar itself. This protection system should work in a sensitive, selective, rapid, and must be stable to disturbance outside the region busbar protection. At the substation Amlapura, if one busbar impaired or absence of the busbar securing safety as on the other substation, will lead to an imbalance perceived by the system and can lead to continuity of power flow can be disrupted. Based on the calculations that have been done shows that for short circuit simulation results busbar A and B obtained Amlapura substation fault current that occurs in the amount of 5.538 kA. For the calculation of the impedance zone 1 (80%) primer is 1.9721 + 5.715 ? A Zsekunder with a time delay of 0 seconds or work instantly, Zone 2 (120%) primer is 5.55 ? Z + J 16.0836 primary, Zone 2 (120%) the secondary is 2.958 + J 8.5726 ? Zsekunder with a time delay of 0.4 seconds. Keywords: Busbar, Rele, Short Circuit Analysis, impedance DOI: 10.24843/MITE.1501.07