Perfecting a Video Game with Game Metrics
Vol 17, No 4: August 2019

Analyzing the deformation of copper conductor from a fire impact

Didik Notosudjono (Pakuan University)
Tatang Kukuh Wibawa (ISTN Jakarta)
Bagus Dwi Ramadhon (Brawijaya University)



Article Info

Publish Date
01 Aug 2019

Abstract

Fire is an oxidation reaction of the three elements (fuel, oxygen, heat) that can result in loss of property, injury, even death. Electricity potential that may results on fire is the short circuit current that occurs on the equipments and electrical installation cables. The remaining wires at the first fire location are subject to fire damage and can cause electrical short circuit. The purpose of this study is to analyze the short-circuit electrical deformation of copper cable using SEM EDS and MICRO XRF instrument. Based on the study result, there is a dominant change of oxygen elements in single cable and fiber sample causing fire that is 35,96% and 21,24%, those values are higher than Oxygen on a burned short circuited cable that is 19,54% and 12,1%. The microstructure of the cable that causes fire looks like irregular clumps whereas the burned cable looks like a clump of clumps.

Copyrights © 2019






Journal Info

Abbrev

TELKOMNIKA

Publisher

Subject

Computer Science & IT

Description

Submitted papers are evaluated by anonymous referees by single blind peer review for contribution, originality, relevance, and presentation. The Editor shall inform you of the results of the review as soon as possible, hopefully in 10 weeks. Please notice that because of the great number of ...