Turbulen : Jurnal Teknik Mesin
Vol.1 No.2 (Des 2018)

PERENCANAAN SISTEM TATA UDARA GEDUNG AULA SMK NEGERI 1 SEKAYU

Andriani, Novi ( Program Studi Teknik Pendingin dan Tata Udara, Politeknik Sekayu)
Hidayati, Baiti ( Program Studi Teknik Pendingin dan Tata Udara, Politeknik Sekayu)



Article Info

Publish Date
31 Jan 2019

Abstract

The planning of the air system is intended to calculate the cooling load in the Hall of SMKN 1 Sekayu. So that before the AC was installed in the SMKN 1 Sekayu had an overview of the amount of AC capacity needed to condition the air in the hall with dimensions of 18 m x 16 m x 6 m. To obtain these results, the authors used the CLTD (Cooling Load Temperature Difference) calculation method based on ASHRAE GRP 158 Cooling Load Calculation Manual. Which consists of calculation of Extenal and Internal cooling loads. Calculation of cooling load based on primary and secondary data which then results are adjusted to the type of air system. After calculating the cooling load, the maximum load results are obtained at 237013,1917 Btu / hr, thus the AC capacity needed is 26 Pk with the Direct Refrigerant System, AC Floor Standing system.

Copyrights © 2018






Journal Info

Abbrev

turbulen

Publisher

Subject

Materials Science & Nanotechnology Mechanical Engineering

Description

Turbulen (pISSN 2621 3354) It's focused on original articles in the form of research results or literature review which provides insight in the field of mechanical engineering and machinery that includes the field study of energy conversion such as combustion engineering, internal combustion engine, ...