Zulkurnain Abdul-Malek
Universiti Teknologi Malaysia

Published : 10 Documents Claim Missing Document
Claim Missing Document
Check
Articles

Found 4 Documents
Search
Journal : Indonesian Journal of Electrical Engineering and Computer Science

Status Review on Gas Insulated Switchgear Partial Discharge Diagnostic Technique for Preventive Maintenance Visa Musa Ibrahim; Zulkurnain Abdul-Malek; Nor Asiah Muhamad
Indonesian Journal of Electrical Engineering and Computer Science Vol 7, No 1: July 2017
Publisher : Institute of Advanced Engineering and Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.11591/ijeecs.v7.i1.pp9-17

Abstract

Gas insulated switchgear (GIS) plays a vital role in high voltage transmission of electrical energy due to its advantages of high reliability and performance, compact in dimensions and outstanding compatibility with the environment. It uses sulphur hexafluoride gas as its insulant and coolant because of its high dielectric strength and excellent arc quenching ability. Gas insulated switchgear in operation suffers the challenge of its insulation decomposition and eventually failure due to the activities of partial discharge that arouses from defects. This failure is catastrophic and it will lead to entire power out stage that will affect all categories of human activities, so there is a need for Gas insulated switchgear condition monitoring and diagnoses in order to carry out preventive maintenance. This paper reviews diagnostic techniques and methods for Gas insulated switchgear insulation degradation caused by partial discharge for the purpose of carrying out preventive maintenance to avert its failure.
Chemical by-Product Diagnostic Technique for Gas Insulated Switchgear Condition Monitoring Visa Musa Ibrahim; Zulkurnain Abdul-Malek; Nor Asiah Muhamad
Indonesian Journal of Electrical Engineering and Computer Science Vol 7, No 1: July 2017
Publisher : Institute of Advanced Engineering and Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.11591/ijeecs.v7.i1.pp18-28

Abstract

Chemical by product diagnostic technique is an efficient, cost-effective and reliable diagnostic technique for gas insulate switchgear condition monitoring in view of its high sensitivity and anti- internal and external electromagnetic interference and noise. In this research paper, coaxial simulated gas insulated switchgear chamber and four different types of artificial defect were designed to cause partial discharge that will simulate the decomposition of sulphur hexafluoride gas in the chamber when energize. Fourier transform infrared spectrometer was used as the method of chemical by-product technique to detect the SF6 decomposition product and its concentration. Different numerous by-products were detected (SO2, SOF2, SO2F2, SO2F10, SiF4, CO, C3F8, C2F6 ) under this experiment using four different types of defect and the by-products differs with the type of defect and the generation rate. Gas insulated switchgear health condition can be feasibly diagnosed by analyzing the decomposition products of SF6 to identify its fault. 
Conductive and Inductive Coupling between Faulted Power Lines and Buried Pipeline by Considering the Effect of Soil Structure Ali I. El Gayar; Zulkurnain Abdul-Malek; Mohammed Imran M; Chin Leong Wooi; Ibtihal Fawzi Elshami
Indonesian Journal of Electrical Engineering and Computer Science Vol 5, No 3: March 2017
Publisher : Institute of Advanced Engineering and Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.11591/ijeecs.v5.i3.pp656-660

Abstract

The AC total interference of faulted power lines to gas pipelines sharing the same right of way, which may pose a threat to operating personnel and equipment, was studied. The main advantage of this work is to determine the effects of different soil structures on the induced voltage for various soil resistivities. Two main approaches were used to compute the induced voltages, namely the method of moment (MOM), which is based on electromagnetic field theory, and the circuit based method, which uses the circuit grounding analysis to compute the conductive interference and the circuit based models to compute the inductive interference. A 10-km-long parallel pipeline-transmission line model was developed. The soil resistivity was varied, and the induced voltages obtained from both approaches were compared. Soil resistivity and soil structure are important parameters that affect the AC interference level. The results of the study show that the earth potentials and the metal GPRS are independent. Higher soil resistivity causes the tower ground resistance to increase, thus making the shield wire’s attractiveness as a fault current return path to increase, which in turn forces the induced net EMF and the cumulative GPR in the pipeline to reduce.
Artificial Neural Network Application for Thermal Image Based Condition Monitoring of Zinc Oxide Surge Arresters Novizon Novizon; Zulkurnain Abdul-Malek; Aulia Aulia
Indonesian Journal of Electrical Engineering and Computer Science Vol 7, No 3: September 2017
Publisher : Institute of Advanced Engineering and Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.11591/ijeecs.v7.i3.pp593-605

Abstract

Manual analysis of thermal image for detecting defects and classifying of condition of surge arrester take a long time. Artificial neural network is good tool for predict and classify data. This study applied neural network for classify the degree of degradation of surge arrester. Thermal image as input of neural network was segmented using Otsu’s segmentation and histogram method to get features of thermal image. Leakage current as a target of supervise neural network was extracted and applied Fast Fourier Transform to get third harmonic of resistive leakage current. The classification results meet satisfaction with error about 3%.