Claim Missing Document
Check
Articles

Found 2 Documents
Search

Studi Manajemen Energi di Rumah Sakit Prima Medika Denpasar Cecep Yudhie Rachmat; I Nyoman Satya Kumara; I.A.D Giriantari
Jurnal Teknologi Elektro Vol 18 No 1 (2019): (Januari - April) Majalah Ilmiah Teknologi Elektro
Publisher : Universitas Udayana

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (1253.899 KB) | DOI: 10.24843/MITE.2019.v18i01.P04

Abstract

Intisari —Rumah Sakit Prima Medika adalah rumah sakit yang telah terakreditasi tingkat nasional dengan katagori tertinggi atau Paripurna di 2016. Dengan tingkat kunjungan pasien tertinggi sebanyak 59.289 orang ditahun 2017 dan tingkat hunian rata rata 79,89% masuk katagori ideal dengan konsumsi energi listrik sebesar 2.299.077 kWh/tahun. Beban kelistrikan berasal dari 5 kelompok peralatan yaitu: kelompok peralatan penerangan 20,08%, peralatan sistem penataan udara 56,12%, peralatan medis 8,92%, peralatan kantor 5,30% dan peralatan utiliti 9,57%. Dari perhitungan audit energi awal diperoleh indeks Intensitas Konsumsi Energi (IKE) sebesar 344,23 kWh/m²/tahun dan ini termasuk dalam katagori Energi Intensive atau menunjukan penggunaan energi yang boros. Akan dilakukan upaya konservasi energi pada semua kelompok peralatan terutama kepada peralatan sistem penataan udara yang merupakan penyerap energi terbesar dimulai dari menyusun asumsi pola jam oprasional peralatan selanjutnya dilakukan upaya pencarian terhadap potensi-potensi hemat energi mulai dari kelompok peralatan penerangan berupa penggantian lampu dengan yang berjenis Light Emitting Diode (LED), dari kelompok peralatan kantor dengan penertiban jam operasional alat Dispenser dan dari kelompok peralatan penataan udara dengan penggantian teknologi AC standart menjadi AC inverter didapatkan total potensi penghematan energi listrik sebesar 613.813,2 kwh/tahun atau sebesar 26,70% sehingga jika usulan Peluang Hemat Energi (PHE) ini dapat diimplementasikan maka nilai IKE akhir dapat menurun menjadi 252,33 kWh/m²/Tahun atau masuk dalam katagori Energy Standart atau sudah efisien.
Studi Manajemen Energi di Rumah Sakit Prima Medika Denpasar Cecep Yudhie Rachmat; I Nyoman Satya Kumara; I.A.D Giriantari
Jurnal Teknologi Elektro Vol 18 No 1 (2019): (Januari - April) Majalah Ilmiah Teknologi Elektro
Publisher : Program Studi Magister Teknik Elektro Universitas Udayana

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.24843/MITE.2019.v18i01.P04

Abstract

Abstract—Prima Medika Hospital is a nationally accredited hospital with the highest category or Plenary in 2016. With the highest patient visit rate of 59,289 people in 2017 and an average occupancy rate of 79.89% is entered into the ideal category with electricity consumption of 2,299,077 kWh / year. Electricity expenses come from 5 equipment groups, namely: lighting equipment group 20.08%, equipment for air arrangement system 56.12%, medical equipment 8.92%, office equipment 5.30% and utilities utilities 9.57%. From the initial energy audit calculation, the Energy Consumption Intensity index is 344.23 kWh / m² / year and this is included in the Intensive Energy category or shows wasteful energy use. Energy conservation efforts will be carried out on all equipment groups, especially to the equipment of the air structuring system which is the biggest energy absorber starting from the assumption of equipment operating hour patterns and then searching for energy-saving potentials starting from the lighting equipment group in the form of lamp replacement with Light type Emitting Diode, from the office equipment group with the control of operating hours of Dispenser equipment and from the group of air structuring equipment with the replacement of standard AC technology into AC inverters, the total potential of electricity energy savings was 613,813.2 kwh / year or 26.70% so if the proposed Energy Saving Opportunity can be implemented then the final value can be reduced to 252.33 kWh / m² / Year or included in the Energy Standard category or already efficient