PERENCANAAN SISTEM PENYALUR PETIR ELEKTROSTATIS DENGAN METODE SANGKAR FARADAY PADA GEDUNG KEUANGAN NEGARA KUPANG Agusthinus S. Sampeallo; Evtaleny R. Mauboy; Yeremias M. Moron
Jurnal Media Elektro Vol 9 No 2 (2020): Oktober 2020
Publisher : Universitas Nusa Cendana

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.35508/jme.v0i0.3207

Abstract

Gedung Keuangan Negara (GKN) of Kupang is the office for the affairs of the state finance and assets. The Franklin type lightning in the State Finance Building is not functioned properly and the value of resistance is quite large plus the number of thunder days in Kupang city reaches 80 thunder days and 128,504 lightning strikes in 2019 according to data from the Kampung Baru Kupang Geophysical Station. The results of primary and secondary data collection according to Indonesian National standards (SNI 03-7015-2004) Gedung Keuangan Negara must be protected from lightning induction because the value of the annual average frequency of direct lightning strikes (Nd) > the allowed local annual lightning strike frequency (Nc). Electrostatic protection is selected for the electrostatic type with a Flash Vectron FV6 type with a radius of 50 to 150 combined with a Faraday cage of 8 finials and funneled through a Bare Cooper conductor 50 mm^2 to grounding system planted in the ground with a rod type electrode diameter of 12 millimeters in length. The electrodes planted varied, namely 0.5 meters, 1 meter and 1.5 meters. The value of grounding resistance R<5 Ω is in accordance with the PUIL 2011 standard. The value of earthing resistance R_average L_(0,5 m)=171,6 Ω, L_(1.0 m)=128,6 Ω and L_(1,5 m)=73,4 Ω. To fulfill the requirements according to the PUIL standard, the number of rods in L_(0,5 m) must be added with the value of R_paralel = 3,7065 Ω for 100 electrode rods, for L_(1 m) with a value of R_paralel= 3,9682 Ω for 70 electrode rods, and for L_(1,5 m)= 3,1708 Ω for 50 electrode rods.
Perencanaan Kebutuhan Distribusi Sekunder Perumahan RSS Manulai II Evtaleny R. Mauboy; Wellem F. Galla
Jurnal Rekayasa Elektrika Vol 10, No 1 (2012)
Publisher : Universitas Syiah Kuala

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (683.142 KB) | DOI: 10.17529/jre.v10i1.145

Abstract

Planning of secondary distribution for residence is important that should consider the load, plan the distribution network, choose the conductor and determine the transformer capacity needed. In this planning, Manulai II Resident is counted as simple household that the transformer is divided into two different areas A and B. Twisted Cable NFA2X size 3x70mm; 3x35mm; 4x25mm; and 2x10mm are used. The research shows that losses and voltage drop are still in tolerance limit and the capacity needed for area A is 50 kVA and 25 kVA for area B.