Analysis Oil Condition of Transformer PT-8801-A by Using the Method TDCG, Rogers Ratio, Key Gas, and Duval Triangle: A Case Study at PT. Perta Arun Gas Rastra Furqaranda; Andik Bintoro; Asri Asri; Waleed Khalid Ahmed Al-Ani; Ashish Shrestha
Journal of Renewable Energy, Electrical, and Computer Engineering Vol 2, No 2 (2022): September 2022
Publisher : Institute for Research and Community Service, Universitas Malikussaleh, Indonesia

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.29103/jreece.v2i2.8567

Abstract

The power transformer would have happened disturbanced that can cause a failure at a transformer. For this condition needed to maintenance power transformer, one of which is by analyzing transformer oil by using the TDCG method. This analysis is carried out to determine the diagnosis of faults in the transformer. This method are the condition of the analysis which is based on the amount of a gas dissolved on oil a transformer. This study used four methods for transformer failure analysis are TDCG method, Rogers-ratio, gas key, and duval triangle. The results obtained by the TDCG method of dissolved   gas are 1332 ppm, the roger’s ratio result a symptom of oil heat a transformer at 300oC, the key gas method results in overheating of oil, and the duval triangle method results in a low breakdown voltage analysis.