Journal of Electronic and Electrical Power Application
Vol 1 No 2 (2021): JEEPA Volume 1 Nomor 2

Analisis Kelayakan Nilai Tahanan Pentanahan Jaringan Distribusi di PT. PLN (PERSERO) ULP Bumiayu

Isnu Gita Kumara (Universitas Peradaban)
Rizki Noor Prasetyono (Universitas Peradaban)



Article Info

Publish Date
04 Oct 2021

Abstract

The grounding system is direct protection against instrumentality and human. The grounding process is carried out using the principle of creating a path for the fault current to the ground and making the equipment have a potential that is close to the value of the ground potential. The supply of a grounding system should be supported by the grounding resistance worth needed by PUIL, which is below 5 Ohm. To maintain the value of grounding resistance, it is necessary to check each 6 months in step with the standards of PUIL. The grounding test was carried out using an earth tester. In the analysis of the 7 grounding points of the PT. PLN (Persero) ULP Bumiayu concluded that there are 4 grounding points that have met PUIL standards because the value of their grounding resistance is below 5 Ohm. Meanwhile, the other 3 points haven't met PUIL standards because they are worth more than 5 Ohm

Copyrights © 2021






Journal Info

Abbrev

jeepa

Publisher

Subject

Control & Systems Engineering Electrical & Electronics Engineering Energy Engineering Materials Science & Nanotechnology

Description

Journal of Electronic and Electrical Power Application (JEEPA) diterbitkan oleh program studi teknik elektro Universitas Peradaban bertujuan membantu mempublikasikan hasil penelitian bidang teknik elektro yaitu : Ketenagalistrikan : pembangit/sumber listrik, transmisi tenaga listrik, distribusi ...