PERAMALAN BEBAN LISTRIK BULANAN SEKTOR INDUSTRI MENGGUNAKAN SUPPORT VECTOR MACHINE DENGAN VARIASI FUNGSI KERNEL Luqman Assaffat
PROSIDING SEMINAR NASIONAL & INTERNASIONAL 2017: PROSIDING IMPLEMENTASI PENELITIAN PADA PENGABDIAN MENUJU MASYARAKAT MANDIRI BERKEMAJUAN
Publisher : Universitas Muhammadiyah Semarang

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (349.449 KB)

Abstract

Electrical energy consumption in the industrial sector is one of the factors that accounted for the production cost, and efficiency of electrical energy use can reduce the production cost. Energy efficiency in industry can be applied by regulating the use of the electric load, it can be watched from the electrical load Characteristics. The monthly characteristics of the electrical load every can be predicted, so do the efforts to regulate the amount of load and provide electrical energy required. This research present the monthly electricity load forecasting in the industrial sector by SVM with a variety of Kernel functions. There are 3 (three) types of training data given on SVM, they are types months of the year, production data and time series data past the electrical load, with a variable input data between 1 year to 6 years. Variations Kernel functions used in SVM methods are Linear, quadratic, Gaussian RBF, polynomial and Multilayer Perceptron. This research produced the smallest forecasting MAPE of 5.33% with a 6 year input data training scheme with Gaussian RBF kernel function. Keyword: Electric Load, Monthly Forecasting, SVM, Kernel Function
EVALUASI DISTORSI HARMONISA TEGANGAN PADA SISTEM TENAGA LISTRIK DI RUMAH SAKIT PANTI WILASA CITARUM SEMARANG Luqman Assaffat
MEDIA ELEKTRIKA Vol 4, No 2 (2011): MEDIA ELEKTRIKA
Publisher : PSTE UNIMUS

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (318.929 KB) | DOI: 10.26714/me.4.2.2011.%p

Abstract

One of the factors that affect power quality is harmonic distortion. Harmonic distortion is measured by the value of Total Harmonics Distortion, THD. THD of Voltage harmonics always be a guide to the basic values of the instantaneous waveform. The research on the evaluation of the voltage harmonic distortion of the power system for Hospital of Panti Wilasa Citarum Semarang is necessary, because the hospital has loads of medical equipment, which requires a voltage supply of good quality, so that the equipment can work with good performance without any equipment malfunctions. Evaluation of voltage harmonic distortion of the power system of Panti Wilasa Citarum Hospital Semarang performed on all three existing MDP. Evaluation results show that these three pieces of existing MDP has Harmonic voltage distortion is still below the limit allowed by the IEEE Standard.Key Words : Harmonics, THD, Harmonics Evaluation
JARINGAN SYARAF TIRUAN SEBAGAI METODE PERAMALAN BEBAN LISTRIK HARIAN DI PT. PISMATEX PEKALONGAN M. Subhan Maulidin; Luqman Assaffat
MEDIA ELEKTRIKA Vol 7, No 2 (2014): MEDIA ELEKTRIKA
Publisher : PSTE UNIMUS

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (632.322 KB) | DOI: 10.26714/me.7.2.2014.%p

Abstract

ABSTRACT Load electricity forecasting of industry can provide an information support to the Top Management and other stakeholders in terms of estimating and monitoring the power requirements and effort in providing it. With the artificial neural network method as an electrical load forecasting method using the short-term power load forecasting in the industrial sector, is expected load forecasting in this study had an average error is small. Research on the daily electricity load forecasting in PT. Pismatex Pekalongan using neural networks with daily electricity load data per hour for one week study. The Result of this study is MAPE of 7.23%. Keywords: Short-Term Forecasting, Electricity Charges, Neural Network
PERBANDINGAN UNJUK KERJA LAMPU JENIS HPL-N DAN SON-T SEBAGAI LAMPU PENERANGAN JALAN UMUM Luqman Assaffat
MEDIA ELEKTRIKA Vol 1, No 2 (2008): MEDIA ELEKTRIKA
Publisher : PSTE UNIMUS

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (186.993 KB) | DOI: 10.26714/me.1.2.2008.%p

Abstract

Penerangan jalan umum diperlukan untuk mempermudah dan membantu manusia dalam melihat obyek di jalan pada waktu malam hari atau suasana gelap. Penerangan jalan umum mempunyai 3 fungsi, yaitu sebagai fungsi keamanan, fungsi ekonomi dan fungsi estetika.Terdapat dua jenis lampu penerangan jalan umum yang sering digunakan selama ini, yaitu lampu jenis HPL – N dan lampu jenis SON – T. Kedua jenis lampu tersebut termasuk ke dalam keluarga jenis lampu tabung atau discharge lamp. Pengujian terhadap unjuk kerja dari kedua jenis lampu tersebut akan dapat memberikan gambaran dan rekomendasi, lampu manakah yang tebaik digunakan sebagai lampu penerangan jalan umum, khususnya jalan utama kota.
EVALUASI PERLINDUNGAN GARDU INDUK 150 KV PANDEAN LAMPER DI TRAFO III 60 MVA TERHADAP GANGGUAN SURJA PETIR Ihwan Ernanto Wibowo; Luqman Assaffat; M. Toni Prasetyo
MEDIA ELEKTRIKA Vol 5, No 2 (2012): MEDIA ELEKTRIKA
Publisher : PSTE UNIMUS

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (914.719 KB) | DOI: 10.26714/me.5.2.2012.%p

Abstract

One of the main causes of damage to existing equipment in the substation was struck bylightning attack that cause the conductor wave and make over voltage and flames leap peak voltage exceeds BIL. The aim of this study was to calculate and analyze the level of protection, against power transformer arrester, the safe distance between arrester and transformer power to get a good protection against harmful lightning surges, comparing both arresters installed. To solve the problems of interference caused by lightning surge lightning arrester is installed as close as possible to put on the transformer clamps to protect electrical equipment. The results of calculations for a distance of 6 m, 4 MBA type 2 arrester capable of with standing the wavefront steepness of 500 kV / μs, while type exlim P 700 kV / μs. The greater the arrester capable of withstanding surge wavefront tilting the better the equipment in substations are protected. The evaluation shows that the distance between arrester and transformer installed in the 150 kV substation Pandean Lamper less than the maximum to protect electrical equipment, especially power transformers.Key words : lightning attack, arrester distance, level of protection.
TINGKAT DISTORSI HARMONISA PADA LAMPU ESSENSIAL YANG BERBEDA MERK Luqman Assaffat
MEDIA ELEKTRIKA Vol 3, No 1 (2010): Electrical Engineering
Publisher : PSTE UNIMUS

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (853.061 KB) | DOI: 10.26714/me.3.1.2010.%p

Abstract

Essential Lamp (SL) is a type of low pressure mercury lamp that worl<s leimlecittirnogn st hines icduer rtehnet tfuubnec atinodn .u Bsiencga uqsne e olefc trtohneic w sowriktcinhg e pqrLinipcmtpinlet , atsh ea ereispelanocsnei amthl eeln adtm isbpcah llcaasargtn ef o boerf classified as a non-linier electrical load It is callIend t hhea remleocntricics .p oHwaermr soynsitcesm ,a rae nmonu lltiinpel_easr olofathdesf rweiqll upernodcyu coe fa na feulnecdtarimcael iptaolwfreerq puoelnluctyio no.f wave. Harmonics generated by tlrc non-linier loads that - power system. So the harmonics will be able to disrupt thwe ipllo owrelur *qiutoatli"4 ta nodf edleelcivlreicreadl ptoow theer sysiems.As a non-linear load, essential lamps produce harmonic distortion, both harmonic currents and voltage- In this study concluded that the dffirent brands of essentiai lamp showed the dffirent value of Total HarmonicsDistortion (fHDKeyuords .Essensial Lamp, Harmonics, THD, power euality, pe Analyzer
PENGUKURAN DAN ANALISA KUALITAS DAYA LISTRIK DI PAVILIUN GARUDA RUMAH SAKIT DR. KARYADI SEMARANG Luqman Assaffat
MEDIA ELEKTRIKA Vol 2, No 1 (2009): MEDIA ELEKTRIKA
Publisher : PSTE UNIMUS

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (267.417 KB) | DOI: 10.26714/me.2.1.2009.%p

Abstract

Rumah Sakit dr Karyadi Semarang merupakan rumah sakit milik Pemerintah Provinsi Jawa Tengah dan merupakan Terbesar di kota Semarang, di mana rumah sakit ini mempunyai peralatan-peralatan kedokteran dan kesehatan yang modern dan canggih. Untuk peningkatan pelayanan kepada pasien dari kalangan yang berada, maka pihak manajemen Rumah Sakit Dr. Karyadi membangun fasilitas rawat inap yang khusus untuk kelas VIP dan VVIP yang ditempatkan pada suatu gedung rawat inap yang bernama Paviliun GarudaUntuk menjamin kenyamanan dan pelayanan kesehatan yang prima bagi pasien kelas VIP dan VVIP tersebut, maka di Paviliun Garuda RS Dr. Karyadi terdapat perlengkapan-perlengkapan kesehatan dan fasilitas-fasilats penunjang lainnya yang memerlukan tenaga listrik. Untuk menjaga kualitas daya listrik pada sistem tersebut diperlukan pengukuran dan monitoring kualitas daya listrik dalam jangka waktu tertentu. Pengukuran kualitas daya ini menggunakan alat A3Q analyzer, di mana dengan alat tersebut dapat dketahui dan dianalisa tentang besaran listrik, bentuk gelombang tegangan dan arus listrik, spektrum harmonisa, daya dan faktor daya, arus netral, kesetimbangan beban.Pengamatan dan pengukuran dilakukan pada Transformator 20 kV/380 V yang khusus mensuplai daya lisrik untuk Paviliun Garuda, Rumah Sakit Dr. Karyadi. Data yang diperoleh kemudian dibandingkan dengan standar yang berlaku dan sesuai dengan nilai yang diijinkan. Dari penelitian disimpulkan bahwa secara umum kualitas daya listrik di Paviliun Garuda Rumah Sakit DR Karyadi Semarang dalam keadaan baik, karena memenuhi syarat yang diijinkan
ANALISA SETTING GROUND FAULT RELAY (GFR) TERHADAP SISTEM PENTANAHAN NETRAL PENYULANG PANDEANLAMPER 06 JTM 20 KV SEMARANG Muhammad Iqbal; Moh Toni Prasetyo; Luqman Assaffat
MEDIA ELEKTRIKA Vol 9, No 1 (2016): MEDIA ELEKTRIKA
Publisher : PSTE UNIMUS

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (458.992 KB) | DOI: 10.26714/me.9.1.2016.%p

Abstract

The operation of the distribution system has major problems in overcoming interference. In its development, electric power systems increasingly large currents cause electrical interference that may occur the greater. Therefore, they invented a system called neutral grounding.There is no ideal grounding neutral earthing throughout the distribution network Semarang cause neutral grounding resistance value. Neutral resistance values may cause a decrease in current flowing to ground disturbance that affects the sensitivity GFR (Ground Foult Relay) installed. Because of that, necessary to analyze the GFR setting the main feeder neutral earthing systems JTM 20 kV feeders Semarang bytaking samples Pandealamper 06 to determine the condition of setting GFR installed in accordance with the neutral earthing systems.Results of the calculation of the noise current by entering the value of resistance neutral earthing exiting GFR values obtained ideal setting on the feeder Pandeanlamper06 is not much different from the existing GFR setting value. Values of 0.27 ? neutral earthing (existing) did not significantly influence the sensitivity GFR of the feeder PDL 06.GFR remaineddetect interference and work in accordance with the characteristic curve GFR.Based on the analysis, GFR mounted setting was appropriate and able to provide security in Pandeanlamper feeder 06.Keywords: Neutral Grounding, GFR, Main Feeder
KORELASI ANTARA MEDAN MAGNET DENGAN TINGKAT DISTORSI HARMONISA PADA MOTOR INDUKSI TIGA FASA Luqman Assaffat
MEDIA ELEKTRIKA Vol 2, No 2 (2009): MEDIA ELEKTRIKA
Publisher : PSTE UNIMUS

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (725.323 KB) | DOI: 10.26714/me.2.2.2009.%p

Abstract

Motor induksi tiga fasa mempunyai rangkaian ekivalent yang sama dengan sebuah transformator, dimana keduanya mempunyai prinsip kerja yang sama yaitu dengan cara induksi magnet yang menghasilkansebuah tegangan. Sebagaimana halnya transformator, motor induksi tiga fasa digolongkan sebagai jenisbeban yang tak linier karena mempunyai sifat kejenuhan magnetisasi sebagai akibat dari penggunaan tipematerial magnetnya.Beban – beban yang tak linier akan menghasilkan suatu polutan daya listrik yang sering disebutdengan harmonisa. Harmonisa diukur dengan suatu tingkatan yang disebut Total Harmonics Distortion,THD, atau dalam istilah Bahasa Indonesia sering diartikan sebagai Tingkat Distorsi Harmonisa. Dari haltersebut dapat diduga bahwa harmonisa yang dihasilkan oleh motor induksi tiga fasa disebabkan olehbesarnya medan magnet yang terjadi. Sehingga perlu dilakukan suatu uji korelasi antara besarnya medanmagnet dengan tingkat distorsi harmonisa pada motor induksi tiga fasa.Hasil pengujian menunjukkan korelasi menunjukkan bahwa Tingkat Distorsi Harmonisa pada motorinduksi tiga fasa, baik THD teganan maupun THD arus, dipengaruhi oleh besarnya medan magnet yangterjadi.
PEMODELAN DAN SIMULASI FILTER AKTIF SHUNT UNTUK PERBAIKAN HARMONISA SEBAGAI UPAYA PENGHEMATAN ENERGI LISTRIK Luqman Assaffat; Sri Arttini D. P.; M. Haddin -
MEDIA ELEKTRIKA Vol 6, No 1 (2013): MEDIA ELEKTRIKA
Publisher : PSTE UNIMUS

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (552.672 KB) | DOI: 10.26714/me.6.1.2013.%p

Abstract

Salah satu metode dalam melakukan penghematan energy adalah dengan memperbaiki kualitas daya listrik. Permasalahan utama dalam kualitas daya listrik adalah permasalahan harmonisa. Harmonisa mempunyai dampak buruk pada sistem tenaga listrik, antara lain terjadinya pemanasan pada trafo, malfungsi peralatan listrik, kesalahan pembacaan pada alat ukur dan kerugian secara finansial. Pengendalian harmonisa pada sistem tenaga dapat dilakukan dengan pemasangan filter harmonisa. Terdapat beberapa jenis filter harmonisa, antara lain filter pasif dan filter aktif. Filter aktif mempunyai kemampuan yang lebih baik dari pada filter pasif karena dapat memperbaiki arus harmonisa sesuai dengan keadaan beban. Pemodelan filter aktif shunt dengan bantuan Matlab/Simulink dan Power System Blocket bertujuan untuk menganalisa berapa besar distorsi harmonisa yang dapat diperbaiki dan besarnya energy listrik yang dapat dihemat. Data simulasi menggunakan data harmonisa pada sistem tenaga listrik Rumah Sakit Panti Wilasa “Citarum” Semarang. Hasil simulasi pemodelan filter aktif shunt menunjukkan bahwa THD Harmonisa arus pada sistem dapat diturunkan sebesar rata-rata 6%. Sedangkan perkiraan energy listrik yang dapat dihemat sebesar 13.692,12 kWH selama satu tahun.