Analisis Sistem Distribusi 20 kV Untuk Memperbaiki Kinerja Dan Keandalan Sistem Distribusi Menggunakan Electrical Transient Analisys Program Abrar Tanjung
Seminar Nasional Teknologi Informasi Komunikasi dan Industri 2012: SNTIKI 4
Publisher : UIN Sultan Syarif Kasim Riau

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (697.65 KB)

Abstract

Electric power is the basic human needs in life. In Indonesia, electricity partly served by the State-Owned Company (PLN) and the other using an electric generator engine with its own power as an energy source, such as: the increasing number of industries and companies in the rapidly growing demand PLN electricity supply must be reliable, inexpensive and economical. With the increasing demand for electricity resulted in the development of generation capacity and transmission line / distribution.The distance between plants with consumers so far the distribution of electrical power through a long transmission line is generally in the form of an open airway, causing disturbances on the electrical system the greater the chance of interference. Such defects if left unchecked will lead to substantial fault current and can disrupt electric power distribution to the consumer. Result and analisys In research to improve the performance and reliability of distribution systems by optimizing the determination of optimum mounting location in PT. PLN (Persero) Cabang Dumai Gardu Hubung Ujung Tanjung for the capacitor 3 x 600 kVAr using program ETAP 4.0.0 version accepted in order to obtain a voltage of 17.6 kV irreparable loss and saving power of 553 kW and 817 kVAr.Reliability level of 0.7638 (index value 76%)Keywords: Distribution systems, capacitors, power loss, voltage drop
ANALISIS KINERJA SISTEM KELISTRIKAN UNIVERSITAS LANCANG KUNING Abrar Tanjung
Seminar Nasional Teknologi Informasi Komunikasi dan Industri 2015: SNTIKI 7
Publisher : UIN Sultan Syarif Kasim Riau

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (364.38 KB)

Abstract

To distribute the electrical power needs of electricity producers to consumers required a distribution network and substations. Based on General Requirements for Electrical Installations ( PUIL ) 2000 and Standard State Electricity Company ( SPLN ), the system can be said to be effective if the voltage drop does not exceed 5 % of the nominal voltage and power loss does not exceed 10 % of the total power supplied The electrical system at the University of Lancang Kuning need to pay attention to large cross-section conductor and conductor prisoners are used to minimize power loss and voltage drop. The reliability of the electrical power distribution system is determined by efforts to minimize power loss and voltage drop occurs in the electrical system. Power loss and voltage drop affects the power distribution capabilities, both of which result from pengahantar channel length between the transformer with the buildings as user load, interference with electrical systems. This study aimed to analyze the voltage drop calculation, over load and power losses and balance the load on the Lancang Kuning University.Results of analysis and calculation of electrical systems Lancang Kuning University gained power loss total of 23.5 kW and low voltage three phase occurred in the law school of 237, 5 volts and load imbalance of the phase R = 199.15 Amper ; Amper phase S = 154.05; and phase T = 121.6 AmperKeywords: electrical system, power losses, voltage drop