Analisis Sistem Sinkronikasi Generator 2x2 MW pada Bandar Udara Haluoleo Kendari Barcelius Londong; Tachrir; Abdul Djohar; Bunyamin; Wa Ode Zulkaidah; Wa Ode Siti Nur Alam; Muh. Nadzirin Anshari Nur
Jurnal Fokus Elektroda : Energi Listrik, Telekomunikasi, Komputer, Elektronika dan Kendali) Vol. 7 No. 4 (2022): Jurnal Fokus Elektroda Vol 7 No 4 2022
Publisher : Jurusan Teknik Elektro Fakultas Teknik Universitas Halu Oleo

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (1444.828 KB) | DOI: 10.33772/jfe.v7i4.70

Abstract

Penerbangan adalah satu kesatuan sistem yang terdiri atas pemanfaatan wilayah udara. Salah satu fasilitas yang sangat penting adalah penyediaan catu daya listrik. Untuk memberikan catu daya listrik dari PLN sangat berpengaruh terhadap penyediaan energi listrik pada Bandar Udara Haluoleo Kendari. Energi listrik dari PLN, tidak selalu continue dalam penyalurannya suatu saat pasti terjadi pemadaman dari PLN. Memiliki catu daya cadangan seperti generator set dengan kondisi generator disinkronisasi termasuk untuk menambah kehandalan. Melakukan penelitian Analisis Sistem Sinkronisasi Generator 2×2 MW. Bertujuan mengetahui apakah sistem sinkronisasi generator sebagai suplai cadangan bisa memback-up beban yang ada. Dari hasil sinkronisasi aliran daya generator unit 1 dan generator unit 2 berbeban pada saat PLN cut off. Sehingga daya terpakai pada generator unit 1 setiap fasa sebesar R: 123,72 kW, S: 123,40 kW, dan T: 126,14 kW, dan daya terpakai pada generator unit 2 setiap fasa sebesar R: 126,12 kW, S: 124,70 kW, dan T: 124,15 kW. Hal ini menunjukkan total beban terpakai Bandar Udara Haluoleo Kendari saat PLN cut off mencapai 80 % dengan daya sebesar 748,23 kW. Berdasarkan hasil software ETAP 12.6.0 simulasi load flow analysis sinkronisasi menunjukkan aliran arus, tegangan, dan daya pada generator. Arus sebesar 878,5 A, tegangan 0,38 kV, dan daya semu 578 kVA, tegangan di naikan pada transformator step up 1000 kVA keluaran sekunder pada transformator step up 19,114 kV, arus 33,7 A, dan daya semu 1117 kVA. Selanjutnya tegangan di turunkan pada transformator step down 1250 kVA keluaran sekunder pada trafo step down 0,35 kV, arus 1776,1 A, daya nyata 915 kW, dan daya semu 1076 kVA. Dengan beban pada Bandar Udara Haluoleo Kendari sebesar 1110 kVA
Analisis Prakiraan Kebutuhan Energi Listrik di Kabupaten Kolaka Utara menggunakan Metode Dkl 3.2, Regresi Linear dan Software Leap Nur Rahmadani; Mustarum Musaruddin; Muh. Nadzirin Anshari Nur; Hasmina Tari Mokui; St. Nawal Jaya; Achmad Nur Aliansyah
Jurnal Fokus Elektroda : Energi Listrik, Telekomunikasi, Komputer, Elektronika dan Kendali) Vol. 8 No. 2 (2023): Jurnal Fokus Elektroda Vol 8 No 2 2023
Publisher : Jurusan Teknik Elektro Fakultas Teknik Universitas Halu Oleo

Show Abstract | Download Original | Original Source | Check in Google Scholar

Abstract

This paper analyses the estimation of electrical energy demand in the North Kolaka Regency for the next few years and also analyses the accuracy of the forecasts from the methods used. The forecast methods used are the DKL 3.2, linear regression methods, and LEAP software with a BAU (Base as Usual) scenario. According to the results of the forecast of electrical energy demand for the upcoming five years using the DKL 3.2 method, there are 192548.29 customers, 31120935.67 kWh of electrical energy consumed, and 236523.48 kVA of connected power, respectively. Using the linear regression method, there are 197753 customers, 22733920.50 kWh, and 235493.40 kVA while using LEAP software, there are 219831.60 customers, 15351429.26 kWh and 274379.50 kVA. While the results of the analysis of the accuracy of the forecast method based on the MAPE and MSE value for the number of customers and the predicted power connected are the DKL 3.2 method, while for the consumption of electrical energy using the linear regression method.
Mekanisme Respon Arus Bocor Isolator Luar Ruangan Di Bawah Pengaruh Iklim Tropis Tambi Tambi; Wa Ode Zulkaida; Muh. Nadzirin Anshari Nur; Fachrur Razy Rahman
Jurnal Fokus Elektroda : Energi Listrik, Telekomunikasi, Komputer, Elektronika dan Kendali) Vol. 8 No. 2 (2023): Jurnal Fokus Elektroda Vol 8 No 2 2023
Publisher : Jurusan Teknik Elektro Fakultas Teknik Universitas Halu Oleo

Show Abstract | Download Original | Original Source | Check in Google Scholar

Abstract

It is important to know the leakage current response mechanism in outdoor insulators when it rains after the dry season to predict the risk of flashover exposed to environmental pollution in aging insulators, so that it can be used as initial information by network maintenance operators to take action in the field. The main objective of this paper is to determine the effect of accumulated pollution and wetting on insulator surfaces on leakage currents at the beginning of the rainy season after the dry season based on real-time monitoring. Monitoring is carried out on polymer silicone rubber-SIR insulators and porcelain insulators installed on transmission towers or on distribution channels on days with drizzling rain and without rain on aging insulators. Based on the leakage current curve and statistical analysis results, drizzling rain during the day and night does not significantly affect the increase in leakage current in the polymer insulator, except when the temperature is above 35 ℃, where the leakage current varies slightly over a wide range.